    The EBC22 is an automatic control with a pressure transducer (XTP) for one or more boilers or other installations where multiple heat sources are connected to the same chimney.

    With the help of the XTP sensors, which are installed in the chimney, the low pressure is monitored and maintained by regulating the speed of the chimney fan.EBC20_web

    The control has inputs and outputs for one or two boilers. With the exodraft ES12 relay box this number can be expanded to up to four boilers.

    The EBC22 automatic also offers the possibility of an external entry point for a pressure switch or alarm sensor as well as the possibility of an alarm exit point for example for a building management system.

    Function

    When the boiler or the heating system starts, a signal is sent to the EBC22 which starts the chimney fan at full speed. When the control receives the signal that the desired chimney vacuum has been reached, a signal is sent to start the boiler’s burner.

    The necessary chimney draft is therefore always guaranteed when you start the boiler, thereby the best and most economical operating conditions are ensured.

    If the chimney draft falls below the required level, the speed of the chimney fan is regulated until the required chimney draft is reached.

    The EBC22 has an external alarm output for integration into a building management system, etc.

    ControlEBC22
    Dimension (H x W x D)204 x 240 x 77 mm
    Weight1,62 kg
    Density class
    Control range0 Pa – 150 Pa
    FuseT 4 A
    Voltage230 V AC, 50 Hz
    Power consumption475 W
    Ambient temperature-20 ºC – +60 ºC
    MaterialABS PA758
    XTP sensor:XTP-150
    Dimension (H x W x D)75 x 92 x 49 mm
    Ambient temperature 0 ºC – +70 ºC
    Max. Distance to EBC20 XTP-sensor100 m
    Density classIP 54
    Inputs Control:EBC22
    Digital inputs (D11 & D12)18 – 230 V AC/DC
    Pressure sensor, input (XTP)0 – 10 VDC, 20 mA
    Pressure switch, input (PDS)24 V DC, 20 mA
    Outputs Control:EBC22
    Digital outputs relay (DO1 & DO2)250 V AC, 8A, AC3
    Motor control, supply voltage motor-3 %, 3A AC3
    Motor start/stop relay250 V AC, 8A AC3
    Control signal 0 -10 VDC20 mA
    Power supply with 24 V100 mA
    DC alarm output relay250 V AC, 8A AC3
    EBC22
    The EBC22 is an automatic control for chimney fans on boilers and large systems. GASTEC-Approved
    Relay boxes

    Relay box for the EBC22 controls. It is possible to connect up to four boilers

    Frequency converters

    Frequency converter FRK008 is used with exodraft RSV400-4-2 chimney fan, and the frequency converter FRK009 is used with the exodraft RSV450-4-2 chimney fan

    Posted by bech_morten / Posted on 04 Jan
  • Post Comments 0